Difference between revisions of "BMC"

From Mesopoly 3.0
Jump to navigation Jump to search
m
Line 7: Line 7:
 
====Description====
 
====Description====
 
The indication of the capacity remaining in the UPS
 
The indication of the capacity remaining in the UPS
−
system's batteries. A value of batteryNormal
+
system's batteries. A value of batteryNormal
−
indicates that the remaining run-time is greater than
+
indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or
−
upsConfigLowBattTime. A value of batteryLow indicates
+
equal to upsConfigLowBattTime. A value of
−
that the remaining battery run-time is less than or
+
batteryDepleted indicates that the UPS will be unable
−
equal to upsConfigLowBattTime. A value of
+
to sustain the present load when and if the utility
−
batteryDepleted indicates that the UPS will be unable
+
power is lost (including the possibility that the
−
to sustain the present load when and if the utility
+
utility power is currently absent and the UPS is
−
power is lost (including the possibility that the
+
unable to sustain the output).
−
utility power is currently absent and the UPS is
+
 
−
unable to sustain the output).
 
 
====Functionality====
 
====Functionality====
 
Trigger a warning if states are between 0 and 1
 
Trigger a warning if states are between 0 and 1

Revision as of 11:58, 6 November 2007

ups monitoring

powerware

Battery Status

OID

.1.3.6.1.2.1.33.1.2.1

Description

The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).

Functionality

Trigger a warning if states are between 0 and 1 Trigger an alarm if states are between 3 and 4

Previously called BMC Patrol BMC Performance Manager Monitoring Studio

Misc